What is the reason for the error message "Error 1800: [Target] [target name] cannot find defined target machine" while downloading through Vijeo Designer ?

This error means while downloading, connection with the target machine could not be established.
Below are the possible reason for this.

When using Serial or USB download, the error message appears due to one of the following:
  • Target machine is OFF.
  • Download cable is not connected to the defined port on the editor PC.
  • Download cable connections are loose.
  • Invalid download cable is used.
  • Download cable is damaged.
  • Connected target machine is not supported.
When using Ethernet download, the error message appears due to one of the following:
  • Vijeo-Designer Runtime is not running or the target machine is not turned ON.
  • You entered an incorrect IP address in the Target's download properties.
  • The IP address set in the Target properties is not for a valid Vijeo-Designer target machine. You probably typed an IP address that belongs to other types of equipment.
  • You used Download All on a project that has more than one target set to the same IP address.

슈나이더 일렉트릭 Korea

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings