브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Unity Pro: Can connection modes be selected?
Issue
There is a need for logging in without the ability to make online edits, but the software defaults to programming mode.

Product line
Unity Pro, Control Expert

Resolution
Unity can be configured to prompt for connection mode so that the programmer can select what he desires. Below are definitions of the choices.

"Use Programming Mode" is the default.  It connects the terminal to the PLC
in programming mode.  If another user is logged into the PLC as the programmer,
the user is offered the option to connect in monitor mode.

"Mandatory Programming Mode".  The terminal connects to the PLC. If another user
is logged into the PLC, the connection is refused, no monitor mode offer is made.

"Use Monitoring Mode". The terminal connect to the PLC in Monitoring only mode.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings