PME 8.0/8.1 VIP hot fix

Issue
A customer is experiencing one or multiple issues with their VIP.

Product Line
Power Monitoring Expert 8.0
Power Monitoring Expert 8.1

Environment
Virtual ION Processor service

Cause
There are three issues which are addressed with this hotfix:

1.  The VIP Data Monitor module events are processed incorrectly. Both ON and OFF transitions generate independent alarms visible in the Active Alarms page in the Alarms web application. The hotfix reverts the VIP Data monitor module back to pre-PME8 behavior, i.e. the Data Monitor module transitions are not treated like alarms, but rather as simple events.
2. The VIP Database Import module will time out on queries that take longer than 30 seconds. The hotfix VIP uses the IONConnectionTimeout registry setting to set the timeout (60 seconds by default)
3. The VIP would interpret large 16 bit values coming from an OPC client incorrectly.

Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

To deploy the attached hot fix follow the steps below:

1) Shut down all PME VIP windows services
2) Rename the existing vip.exe in the \system\bin directory.
3) Copy in the updated version of vip.exe
4) Restart the VIP services

슈나이더 일렉트릭 Korea

첨부 파일
VIP_Hotfix.zip [1.12 MB]
자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings