How do I troubleshoot the Altivar Process Drive when it will not connect or communicate while over a Modbus Serial Network?

Resolution:

If your drive is not connecting or communicating over a Modbus serial network, the issue is typically related to wiring, network configuration, communication settings, or control setup. Use the steps below as a basic troubleshooting guide.

Drive Will Not Connect

1. Verify Installation

  • Ensure a Modbus serial cable (not Ethernet) is connected to the correct port.
  • Confirm proper pin wiring based on the required pinout.
  • Minimize electrical interference:
    • Use separate conduits for control and power wiring
    • Add terminating resistors if the drive is the last device on the network

2. Check Network Configuration

  • Make sure there are no duplicate Modbus addresses on the network.
  • Verify all network devices are properly configured and compatible.

3. Confirm Drive Communication Settings
In the drive settings, verify:

  • Modbus Address
  • Baud Rate
  • Other serial parameters (parity, stop bits if applicable)

After making changes, always power cycle the drive.

4. Check Status Indicators

  • Review the drive’s LED indicators:
    • The Modbus (Eth NS) LED shows communication status
    • Use LED behavior to confirm if the network is active or faulted. Eth NS (Embeded Modbus) - Indicates the Modbus serial link connection status​

​Frontal LEDs​

Drive Connects But Will Not Run

    1. Verify Communication

    2. Check Control Configuration

    • Confirm the drive is set to Network Control
    • Path: [Complete Settings] → [Command and Reference]
    • Verify:
      • Command source
      • Frequency reference source

    3. Review Communication Mapping

    • Navigate to: [Display] → [Communication Map]
      Ensure the correct registers are assigned for command and reference values

    4. Validate Command Channels

    • Check:
      • Command register
      • Reference frequency channel
      • Reference frequency value
    Most Modbus communication issues result from incorrect wiring, mismatched communication settings, or improper control configuration. Systematically checking each area—hardware, network, and programming—will help restore proper communication.

    If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

    Frequently Asked Questions - Schneider Electric (se.com)

    If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us atdrive.products.support@se.comto create a case with our Technical Support Team.

    If you are not located in North America, please contact your local Customer Care Center for assistance:

    Support | Schneider Electric Global (se.com)

    슈나이더 일렉트릭 Korea

    첨부 파일
    ATV900_Programming_Manual_EN_NHA80757_02.pdf [11.22 MB]
    ATV Process MB serial 11_2014.pdf [5.01 MB]
    ATV600_Programming_Manual_EN_EAV64318_04.pdf [10.52 MB]
    ATV900_Modbus_SL_Manual_EN_NHA80939_01.pdf [1.38 MB]
    자세히 알아보기
    제품군
    자세히 알아보기
    제품군
    • 제품 문서
    • 소프트웨어 다운로드
    • 제품 선택기
    • 제품 대체 및 교체
    • 지원 및 연락처 센터
    • 영업소 검색
    • 견적 받기
    • 슈나이더 일렉트릭 커뮤니티
    • 채용
    • 회사 소개
    • 부정 행위 보고
    • 접근성
    • 뉴스룸
    • 투자자
    • Ecostruxure
    • 작업 검색
    • 블로그
    • 개인정보 취급방침
    • 쿠키 공지
    • 사용 약관
    • Change your cookie settings
    • 환경설정 센터