Can the SoMachine V4.3 / EcoStruxure Machine Expert array size be changed at runtime?
Issue
I would like to have a dynamic array size during runtime of my SoMachine or EcoStruxure Machine Expert PLC. How is this done?

Product
SoMachine
EcoStruxure Machine Expert

Environment
PLC Configuration Software programming

Resolution
This can be achieved by assigning a Symbol (tag/variable) inside the definition of the array.
Example - this is the declaration of a dynamically sized Array of INTs:

VAR
iArrayIndex1 : INT;
MyIntArray : ARRAY [0..iArrayIndex1] OF INT;
END_VAR

NOTE:
1) Dynamic Arrays will not work with variable sharing to HMI via the Symbol Configuration Node. Vijeo Designer and EcoStruxure Operator Terminal Expert do not handle Dynamic Arrays.
2) If you are using Dynamic Arrays inside Functions or Function Blocks, the instantiated memory size for a called Function or Function Block is limited, so limit the maximum value of the index accordingly and test your application thoroughly.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings