Can I test a high horsepower ATV900 series drive on an undersized motor?

Article available in these languages: 스페인어

Issue:
Need to bench test an ATV900 series drive but only have an undersized motor available.  What parameters in the drive need to be changed in order to run the drive on an undersized motor?


Product line:
ATV600 / ATV900 series process drives.

Environment:
All models, All serial numbers.

Cause:
Information not available in current literature.

Resolution:

Note that this is for testing purposes only and can not be used as a permanent configuration.

Select control law to CTT = UF5pt
It is not necessary to enter the 5 points.

Enter name plate in cos MPC = cos
Adjust FRS parameter to match the motor rated frequency in Hz.
Adjust UNS parameter to match the voltage rating of the motor, not the voltage of the incoming 3 phase power.
DO NOT PERFORM AN AUTOTUNE.

Reduce current limitation : CLI = FLA of motor, or as close to it as you can adjust it.
Reduce IR compensation  : UFR=0
Slip compensation to SLP= 0
Reduce the inertia factor  : SPGU = 0
Disable the boost BOA = Inactive

This should allow you to run the drive on an undersized motor for testing purposes, such as verifying you control scheme. Do Not use this configuration as a permanent configuration as motor damage could occur.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings