Does Vijeo Designer Support the Allen Bradley Micro800 series PLCs?

Article available in these languages:

  • 스페인어
  • , 일본어

Issue:
Unable to find documentation regarding support for the Allen Bradley Micro800 series in Vijeo Designer.

Product Line:
Vijeo Designer (all versions)

Resolution:
Vijeo Designer currently does not support the Allen Bradley Micro800 series of PLCs natively. In order to program a Magelis HMI to talk to the Allen Bradley Micro800 series of PLC, we must use the Modbus TCP/IP protocol. In other words, the Modbus Communication module must be installed on the Allen Bradley Micro800 PLC and the Vijeo Designer application must use the Modbus TCP/IP driver.

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.