Can I connect more than one Coordinator to the NetBotz Rack Monitor 250 wireless sensor network?
Issue
Each wireless sensor network must have one and only one Coordinator, connected only to the designated Wireless port on the Rack Monitor 250.
The Coordinator for the wireless sensor network on the NetBotz Rack Monitor 250 is under a plastic cover, connected to the port labeled Wireless. This is the only Coordinator allowed on the wireless sensor network.
Connecting an additional Coordinator to any other USB port on the appliance disables the Coordinator connected to the Wireless port.
Product Line
NetBotz Rack Monitor 250
Environment
NetBotz Rack Monitor 250
NetBotz USB Coordinator & Router
Cause
A firmware issue allows the Coordinator to enumerate when it is connected to a USB port other than the designated Wireless port.
Resolution
Use the Coordinator connected to the Rack Monitor 250 Wireless port as the only Coordinator on the wireless sensor network.
게시 대상: 슈나이더 일렉트릭 Korea


도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.