How many TCP connections does the Unity Momentum Ethernet port suppport?
Title
TCP connections supported by the Unity Momentum
Issue
TCP connections supported by the Unity Momentum
Product Line
Unity Momentum PLC
Environment
Unity
Cause
N/A
Resolution
The Unity Momentum Ethernet port can support 16 concurrent client connections and 16 concurrent Server connections.
Any PLC/SCADA sending a request to a Unity Momentum via Ethernet is connecting to one of the Unity Momentum Ethernet port's TCP Server connections.
If a Unity Momentum Ethernet port is issuing a ModbusTCP request to a remote node via a programmed MBP_MSTR blocks then that Unity momentum is using one of the TCP Client connections .
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.