Video: How do I customize short message e-mail alarm actions in Data Center Expert?

Issue:
Customizing short message e-mail alarm actions in StruxureWare Data Center Expert

Product Line:
StruxureWare Data Center Expert (DCE)

Environment:
StruxureWare Data Center Expert (DCE)

Cause:
E-mail notifications from DCE come in a pre-defined format that can not be edited.  To customize e-mail notifications, short message e-mail alert actions need to be used.

Resolution:



1) Open the DCE Client and go to: Alarm Configuration menu > Manage Alarm Actions.

2) Click on Create and then select Short Message E-Mail.  Select Next.

3) Provide an Action Name and add in the e-mail addresses that this alarm action will be sent to.

4) The subject and message fields can be customized using a defined list of macros, which are available on

https://community.se.com/t5/Manage-Alarm-Actions/Alarm-macros-for-SMS-email-alarm-action-settings-on-the-DCE/ta-p/461096

NOTE: You can use spaces, text, and return lines to organize the data that will be sent in the e-mail.

5) Associate your new alarm action to a notification policy, for instructions see Data Center Expert | Video: How do I configure StruxureWare to send e-mail notifications?

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
제품군
자세히 알아보기
제품군
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings