Product Line
Power Monitoring Expert
Environment
Event Watcher Manager and Web Applications
Resolution
Step 1. Enter Subscription Email Configuration (SMTP Server, "From" Display Name, "From" Display Address)
- Launch Management Console
- Enter username, password
- Select Tools >> Reporting Configuration >> Reporting Configuration Manager
- Click on the Subscriptions Tab
- Enter the SMTP Server IP address, "From" Display Name, and "From" Email Address
- Press OK
Step 2. Create the Alarm
- Within Management Console, select Tools >> Reporting Configuration >> Event Watcher Manager
- Configure alarm using Event Watcher Manager
- Select New
- Give the alarm a name
- Select the appropriate template
Note: Custom templates can be created using the Template tab. For example a common use case is for Sag/Swell events only, please see FA407306.
- If desired, give the alarm a description
- Select the device(s) that the alarm will apply to
- Press OK
Step 3. Create the report subscription
- Launch Web application
- Enter username, password
- Click on Reports tab
- Create, Run and save the desired report:
- In the Report Library, Select Report type (or create a new one)
- Setup the report parameters
- Generate the report
- Click Save button
- Select the save location and press OK
- Create the report subscription:
- Click on Subscribe
- Customize the subscription name
- Select an output format of email
- Click Distribution list
- Enter the email address of each desired recipient
- Optional: Enter a subject for the email
- Under subscription schedule, select On Alarm
- Set deliver report on alarm to the alarm created in Step (1)
- Optional: You can click on
to test the alarm.
- Click Save
- Click on Subscribe