How to change the node name of a M241 and M251 with an SD card?
Issue:
How to change the default node name of a SoMachine / Machine Expert controller via an SD card
Product line:
M241
M251
Environment:
SoMachine 4.3
EcoStruxture Machine Expert
Resolution:
1. In SoMachine or Machine Expert/ Logic Builder go to Project / Mass Storage (USB or SDCard) in the main menu
2. Click on Add new ( + yellow sign)
3. Click on Choose a command and select SetNodeName
4. Enter the desired node name in the Device name field
5. Click on Generate and select your SD card or a place where to generate the files that will be later moved to the SD card
Notes:
- The method for this FAQ was verified with SoMachine 4.1 SP2, SoMachine 4.2, SoMachine 4.3, Machine Expert 1.2, Machine Expert 2.0
- The node name can also be change when online with your controller by going to Device window / MyController / Communication settings tab. There right-click on your controller and select "Change device name..." to change the NodeName
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
How to change the default node name of a SoMachine / Machine Expert controller via an SD card
Product line:
M241
M251
Environment:
SoMachine 4.3
EcoStruxture Machine Expert
Resolution:
1. In SoMachine or Machine Expert/ Logic Builder go to Project / Mass Storage (USB or SDCard) in the main menu
2. Click on Add new ( + yellow sign)
3. Click on Choose a command and select SetNodeName
4. Enter the desired node name in the Device name field
5. Click on Generate and select your SD card or a place where to generate the files that will be later moved to the SD card
Notes:
- The method for this FAQ was verified with SoMachine 4.1 SP2, SoMachine 4.2, SoMachine 4.3, Machine Expert 1.2, Machine Expert 2.0
- The node name can also be change when online with your controller by going to Device window / MyController / Communication settings tab. There right-click on your controller and select "Change device name..." to change the NodeName
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)
게시 대상: 슈나이더 일렉트릭 Korea






도움이 필요하신가요?
제품 선택기
애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.
견적 받기
영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.
구매처
해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.
지원 센터
한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.