Why i get error ' The variable isn't modifiable' while trying to deselect the option " exchange on STBY " in variable editor of unity pro ?
The variables declared in unity pro must not be located type with addresses assigned to it.
You need to use unlocated variables and after that uncheck options gets available for exchange on STBY.