How to upload or download files on ATV630/ATV930 drives using VW3A1111.
Issue:
Transferring files using VW3A1111 on the Process Drives
Product Line:
ATV600 and ATV900 series
Environment:
All models
Cause:
N/A
Resolution:
Save to HMI (Keypad)
From the main menu, Go to [File management] [Transfer config file] [Copy from the Drive]
Transfer Back to the Drive From HMI
From the main menu, Go to [File management] [Transfer config file] [Copy to the Drive]
PC
Plug HMI to PC with mini USB connector and open HMI folder and go to (DRVCONF) folder and open .cfg file