How much memory does a single data log value consume within PME?
Issue
How much memory does a single data log value consume within PME?

Product Line
Power Monitoring Expert (PME)
StruxureWare Power Monitoring (SPM)
ION Enterprise (ION-E)

Environment
SQL server databases

Resolution
This value can vary based on the installed version of PME for the system, but this can be checked through SQL Management Studio.

** Warning:  Only those familiar with SQL server and PME should be working with SQL Management Studio.  Making direct modifications to the PME databases can leave a system inoperable and require restoration from backups. **

1)  Log in to SQL Management Studio
2)  Expand the databases folder, right-click ION_Data, select Reports < Standard Reports <  'Disc Usage by Top Tables'

SSMS Reports Table

3) This will produce a report that shows the memory usage per table within the database as shown below.

SSMS Reports Table 2

4) Divide the number of records by the Data (KB) column for the DataLog2 table.  This will give an approximate value of the memory usage for a single-row entry.
2,265,592 / 95,808 = 23.6472110888, so each row entry within the DataLog2 table consumes approximately 23.67 kilobytes of hard drive space.
This example was taken from a PME 8.1 test system.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings