브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Can you convert settings from an ATV32 or ATV312 program into an ATV320 using SoMove Software?

Article available in these languages: 터키어

Issue:
Convert settings from an ATV32 or ATV312 program into an ATV320 using SoMove

Product Line:
ATV32, ATV320, ATV312

Environment:
All models, all serial numbers

Cause:
N/A

Resolution:
Yes, please follow the instruction steps below:
  1. Open Somove and from the Home Screen, click on [Device Conversion] button on the left under tools
  2. Choose your source ATV32 or ATV312 file that you want to convert.
  3. Choose your target location (ATV32 to ATV320) or (ATV312 to ATV320)
  4. Change target DTM to ATV320
  5. Choose Convert
  6. Choose if you want the B suffix or the C suffix version ATV320 drive.
  7. Option window comes up to allow you to save changes to txt file.
  8. Skip saving the changes and continue
  9. Now your new ATV320 file comes up, and you can save this new file to your PC
  10. File menu, choose Save as enter and name your new file to save.




슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings