오늘 무엇을 도와드릴까요?

What is the unit of LCR register in Altivar Process ATV600/ATV900 variable speed drive?

Register LCR in Altivar Process ATV600/ATV900 is in fixed point format. According to drive rating there are 2 or 1 or 0 decimal digits.

So, the unit is:
up to 15 kW : 0.01A;
18kW to 160kW : 0.1A;
220kW and more : 1A;


The reason for this is limited range of the register and accuracy of AD converters.

The LCR register in Altivar Process ATV600/ATV900 drives provides motor current feedback used for monitoring and diagnostics.

Its value is not stored as a floating‑point number but as a fixed‑point format, where the number of decimal places depends on the drive’s power rating.

The unit and decimal resolution of the LCR register is drive‑rating‑dependent:

Drive rating (ATV600 / ATV900)

Decimal resolution

Register unit

Up to 15 kW

2 decimal digits

0.01 A

18 kW to 160 kW

1 decimal digit

0.1 A

220 kW and above

0 decimal digits

1 A

Interpretation example:

  • If LCR = 2534 on a 15 kW drive → 25.34 A
  • If LCR = 253 on a 55 kW drive → 25.3 A
  • If LCR = 25 on a 250 kW drive → 25 A

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터