오늘 무엇을 도와드릴까요?

How to solve a blue screen issue at the iPC startup after installing the NI-VISA software?

With the new iPC range, we get a blue screen issue at the iPC startup after installing the NI-VISA software.
This issue comes from a conflict between the system monitor driver and the National Insturment software, meaning users cannot use the system monitor function and the NI software at the same time.

Short Term Solution:
If customers use our images, they will have to disable system monitor driver in Device Manager before installing NI software, the downside is they will not be able to use system monitor function anymore. If customers need to use system monitor function, they have to remove NI software since both software cannot co-exist.

>> Open “Device manager”, disable “SUSI4 Driver” under “System devices” (see attached screenshot).

New iPC offer:
- Standard references: HMIBMPxxx, HMIPMUxxx, HMIPSPxxx, HMIPEPxxx, HMIPSOxxx
- Configured references: HMIPCCU2xxx, HMIPCCP2xxx, HMIPCCS2xxx

슈나이더 일렉트릭 Korea

첨부 파일
Capture.PNG.png [119.6 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터