브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to convert the Float 32 Format to decimal.

Issue:
User needs to convert a Float 32 register value into a decimal number

Product:
ION and Powerlogic Meters

Environment:
Arithmetic Conversion

Cause:
Some registers are stored as Float 32 values. In order to make sense of that value we have to convert that number to a decimal value.

Resolution:
Float 32 values will take 2 registers, if you check in the Register List.

  1. So, to start with convert the values separately in both the registers to Hexadecimal.
  2. Now, use the below link and use the value in the registers in ascending next to each ​​​​​​

https://www.h-schmidt.net/FloatConverter/IEEE754.html

Below is an example of the process:

For Registers,
3000 - 5EF3
3001 - 4323

Input the hexadecimal box of the link as 5EF34323 to get the exact decimal values. 8.7644463E18

Attached document screenshot for further reference.


슈나이더 일렉트릭 Korea

첨부 파일
IEEE 754 Converter.pdf [150.59 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings