Unity Pro: coil not well animated on specfic LD network
On some very specific networks like below, the coil does not get the right value.
This problem comes when the Project Settings//General//Build settings//Generate with LD link animation
is not selected.
To work correctly the Project setting Generate with LD link animation must be checked.
This problem is corrected in Unity Pro V12.0.
This problem comes when the Project Settings//General//Build settings//Generate with LD link animation
is not selected.
To work correctly the Project setting Generate with LD link animation must be checked.
This problem is corrected in Unity Pro V12.0.