오늘 무엇을 도와드릴까요?

How to calculate the ‘Delay Between Frames’ value for the inter-character gap time on a Unity Momentum serial Modbus port

Issue
The Modbus slave RS232 serial port of a legacy Momentum (Concept based program) does NOT adhere to the inter-character gap timing in RTU mode.  The Modbus slave RS232 serial port of a Unity Momentum (Unity based program) does adhere inter-character gap timing in RTU mode.

Because of this difference, a Unity Momentum that replaces a legacy Momentum PLC used in radio/modem communications, may result in an increase in communication errors or limited operation.


Product Line
171CBU78090
171CBU98090
171CBU98091



Resolution
One solution may be to increase the Delay Between Frames, aka 'inter-character gap', timing of the slave port.  For example, to achieve an inter-character gap of 20ms, the Delay Between Frames value must be changed from its default value of 4 to 47.  This does not mean the delay was increased from 4ms to 47ms.  It is a value that results in a specific inter-character gap time calculation.

To determine the value required for a specific inter-character gap time, the following equation is used.  The example below shows how a value of 47 was calculated for a 20ms inter-character gap requirement.

(Delay Between Frames value = (7 x intercharacter gap required in ms) / 3)

Delay Between Frames value = [7 x 20ms] / 3)
Delay Between Frames value = [140 / 3)
Delay Between Frames value = 46.6  (47)

The result is then entered into the 'Delay between frames' field (as indicated below).


Configuration screen




슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings