How do I program a relay to close on the ATV61 / ATV71 series drives when a specific motor frequency is reached?
Issue:
ATV61/ATV71 relay configuration

Product Line:
ATV61 / ATV71 series drives.

Environment:
All models, All serial numbers

Cause:
Information unclear in existing documentation.

Resolution:
Use Frequency Threshold Attained.
Under menu 1.5 - Inputs/Outputs CFG, select the relay you wish to use (R1 to R4 Configuration) and press Enter (the dial button).
Go to Relay (x) Assignment and select Freq. Th. attain (FTA).

Next, navigate to back to the Drive Menu and select Menu 1.3 - Settings and scroll down to parameter Freq. threshold (FTD).  Adjust this value to the frequency at which you want the relay to energize.
The assigned relay will energize any time the motor output is at or above this frequency and de-energize when running below this frequency.

i.e - Assign R2 to Freq Th. attain.  Set Freq. threshold to 40Hz.  When the drive reaches 40Hz, the R2 relay will close.  This will stay closed until the frequency drops under 40Hz.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

  • 제품 선택기

    애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

  • 견적 받기

    영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

  • 구매처

    해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

  • 지원 센터

    한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings