오늘 무엇을 도와드릴까요?
What is the External Error (EPF1) fault on the Altivar Process Drive?
Resolution:
Probable Cause
- Event triggered by an external device, depending on user.
- An external error has been triggered via Embedded Ethernet
Remedy
- Check External Fault settings
- [Complete settings] -> [Error/Warning handling] -> [External error]
- External error assignment. If the assigned bit state is:
- 0: there is no external error.
- 1: there is an external error (EPF1)
- Check Embedded Ethernet settings
- [Communication] -> [Comm parameters] -> [Embd Eth Config]
- A faulty or duplicate address can cause conflicting issues.
- Try setting a different fixed IP address
- Check Network or PLC settings for any other conflicts
- Check for any possible electrical interferences
If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)
If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.
If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com
게시 대상: 슈나이더 일렉트릭 Korea