브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
What is the InF9 or internal error 9 on the ATV630 and ATV930 Process Drives?
Issue:
Internal Fault Error (InF9) on the Altivar Process Drives?

Product Line:
Altivar Process Drive (ATV630, ATV930, ATV650, ATV950, ATV660, ATV960, ATV680, ATV980)

Environment:
All serial numbers for Altivar Process Drive

Cause:
N/A

Resolution:
Principle
The fault indicates that the current measurement are not correct

Probable Cause
  • Bad Current Circuit/Sensors
  • Bad Control/Power Board
Remedies
  • For customers who are not familiar with the drive please contact your local Schneider Electric Representative.
  • If those who are more familiar with the Altivar Process drive you can follow procedures below:
    • Check ribbon cable between control board and power board
    • Swap power board or control board
    • Change out current sensors
    • Replace/repair complete drive

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings