브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Video: How to upload and save the project file from the Twido PLC?

Article available in these languages: 일본어

Issue:
How to transfer a project file from the Twido PLC to the PC.

Product Line:
Twido Controllers and TwidoSuite Software.

Environment:
TwidoSuite

Resolution:
The Twido PLC powered on,
The communication cable TSXCUSB485 + TSXCRJMD25 (USB to RJ45 to RJ45 to minidin8) and the programming software TwidoSuite.

1) Run the TwidoSuite and choose "Programming" mode
2) From the "Project" tab, click "Open an existing project"
3) Check "From Controller",
4) Then click "Load".
5) The TwidoSuite will then jump to the "Select connection" page, choose your com port and click "OK".
6) Then the program existed in the controller will be transferred to the PC.
7) To save the project, you need to disconnect the PC from the PLC first. After this is done, the "Save current project" selection should be available from the "Project" tab.
8) Finally, select the location and file type to save your project.

NOTE: Twido is obsolete and the recommended replacement would be the Modicon M221 Nano PLC with EcoStruxure™ Machine Expert (formerly Somachine Basic) and can import the Twido program.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings