브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Video: How to configure the "DIAGNOSE Mode" of “RENF22R2MMW NFC Timing Relay” product using smart phone?
Step 1 : Product Identification
Step 1.1 Initiate the NFC App
Step 1.2 Select the Read button
Step 1.3 Place the phone in front of NFC Timing Relay.
And adjust the phone until the “Pairing Indication LED” lit-up.
Step 1.4 Below screen appeared when Uploading is successfully executed.

Step 2 : Function & Timing selection
Step 2.1 Select the Function C. Off-delay relay with control signal
Step 2.2 Press the T button and set T = 35s

Step 3 : Loading the DIAGNOSE Mode
Step 3.1 Select <Diagnose> button.
Step 3.2 Press the Read button. Place the phone in front of NFC Timing Relay.
Step 3.3 Below message appeared after Uploading is successfully executed.
Step 3.4 4 - Power Supply Indication (green) LED
Fast Blinking….
to indicate that the product is on <DIAGNOSE> Mode.


슈나이더 일렉트릭 Korea

첨부 파일
DIAGNOSE Mode_Presentation.pdf [1.18 MB]
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings