How to reset the SmartConnect Communications/Network Interface

Article available in these languages:

  • 스페인어
  • , 프랑스어

Issue:
How to reset the SmartConnect Communications/Network Interface

Product Line:
SmartConnect enables Smart-UPS

Environment:
Smart-UPS SMC, SMT, SMTL, SMX, SCL, SRTL with built-in SmartConnect network port

Cause:
Need to reset for X reason, or need to establish or re-establish connectivity with the SmartConnect cloud communications with PowerChute.

NOTE: Resetting the communications interface won't affect the load attached. AC output will continue.

Solution:
To reset the communications/network of an SMT, SMTL, SMX, or SRTL model UPS on the display interface, hold the UP and DOWN buttons simultaneously for 10 seconds. The display flashes to indicate that the network interface has restarted.

SMT1500C Front Panel

NOTE: For SMT1500RM1UC models, to reboot the network interface, reset the UPS. See FAQ FA156611

To reset the communications/network interface of an SMC model UPS, hold the MUTE and MENU buttons simultaneously for 10 seconds on the display interface. The display flashes to indicate that the network interface has restarted.
SMC1500C
SMC1500C

To reset the communications/network interface of an SCL model UPS, insert a paperclip into the reset hole on the rear of the UPS.
SmartConnect network port image

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings
  • 환경설정 센터