Are there status words available which will allow me to see module health on the ERIO network?
Issue:
Are there status words available which will allow me to see module health on the ERIO network?
Product Line:
ERIO network, Quantum, Modicon
Resolution:
Yes, the following System Words will provide the health status of each IO module on the ERIO network.


%SW641-702   Referred to as ERIO Module Health (refer to Unity Help for detail as to which words apply)
16 bits of the word represent the 16 potential slots in a Quantum backplane.
0 = unhealthy or not mapped
1 = healthy module.

R-2192018