브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to Upgrade PM8000/ION7400 Webpages

Issue
How to Upgrade PM8000/ION7400 Webpages

Product Line
PM8000/ION7400

Environment
PM8000/ION7400 Webpages

Cause
Need restore or upgrade the webpages on a PM8000 or ION7400 meter.

Resolution
To update/upgrade the meter webpages you will first require:

  • Webpage upgrade files, they can be downloaded from the Schneider Electric Download Center. To locate them, enter PM8000 webpages or ION7400 in the search bar, then search for Firmware and Associated Files. Review the release dates to select the most appropriate version for your device.
  • access to the meter's internal SFTP site
  • Refer to the most up-to-date documents (as of December 26, 2025) available in the Related tab.

To perform the update/upgrade:

  1. Connect to the meter's internal FTP site and open the webpages (web) folder
  2. Navigate to the location on your local machine where you have saved the webpage update/upgrade files
  3. Drag the resources and example folders into the web folder you opened in step 1.  Confirm to overwrite existing files when prompted.  Once confirmed, the files are then immediately transferred to the meter. If the entire folders are replaced (ie. deleted and re-added) to the meter's web folder any custom content will be lost.

For more information on meter webpages or connecting to your meter's SFTP site, refer to the user manual for your particular meter.

슈나이더 일렉트릭 Korea

첨부 파일
ION7400_MID_webpages_V004.006.000.zip [803.67 KB]
PM8000_webpages_V004.006.000.zip [803.67 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings