오늘 무엇을 도와드릴까요?

How to replace an IFM TRV00210/STRV00210 by an IFM LV434000?

The IFM was updated with several improvements and changes in the design. The firmware in both units is backwards compatible with existing installations.  In addition, the new module, LV434000, is future ready as it is designed to work with the Masterpact MTZ. See detailed differences in FAQ FA321260.

Mainly impact for substitution is the Modbus connector (5-pin connector on TRV00210/STRV00210 and RJ45 for new reference LV434000)

You can then use the following accessories to operate substitution:
  • VW3A8306D30: Cables: Rj45-open
  • VW3A8306TF03 or VW3A8306TF10: T connector 3 or 10 meters
  • VW3A8306RC: Modbus line Terminator

See examples for the following cases:
<3m>3m
CentralizedWith IFEUse Case B1Use Case B4
Without IFEUse Case B2Use Case B5
DistributedUse Case B3Use Case B6

슈나이더 일렉트릭 Korea

첨부 파일
New IFM use case B1-B2.png [79.75 KB]
New IFM use case B3.png [85.23 KB]
New IFM use case B4-B5-B6.png [89.87 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings