How do I transfer programs from one ATV630/930 series drive to another with the VW3A1111 graphics keypad?

Article available in these languages:

  • 일본어

Issue:
Transfer programs from one ATV630/930 series drive to another with the VW3A1111 graphics keypad

Product Line:
Altivar 630/930

Environment:
All

Cause:
N/A

Resolution:
Please note:When transferring programming, the following must be the same for all drives involved:
  • drives' part numbers
  • firmware versions
  • wiring setup
  • option cards
  • revision "rev" number
  • IP rating
All the above have to match exactly. Otherwise, you will get a configuration error.

To copy the drive's programming to the keypad:
From main menu, go into menu 7 'File management'
Enter menu 7.1 'Transfer config file'
In this menu you have 2 options:
  • 'Copy to the drive' (from the keypad)
  • 'Copy from the drive' (to the keypad)
When the program is copied from the drive to keypad, the drive gives you the option to name the file. The filename can be whatever you want.
Press OK to continue.

Disconnect the keypad from the drive and connect it to the drive to which you want to copy the programming.

Downloading from the keypad to the drive is similar:
From main menu, go into menu 7 'File management'
Enter menu 7.1 'Transfer config file'. In this menu choose 'Copy to the drive'
The drive will prompt you to choose which file you want to use so it is important to remember the name of the file you saved to prior.
Select the file you wish to use and press OK

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings