오늘 무엇을 도와드릴까요?

Why do I get the build error " The instance is located on an address that is not configured " in Unity Pro.

Issue:
Unity Pro/EcoStruxure Control Expert build error " The instance is located on an address that is not configured"


Product Line:
Unity Pro/EcoStruxure Control Expert


Resolution:
For Flat Memory mapping:
This error is generated when you are using a memory address %I,%M, %IW or %MW located on a variable that is greater than the configured amount. You must increase the configured amount of memory address in the processor configuration.

For Topological addressing:
This mean that the address entered for the variable is not located to any IO modules. It the address looks correct to you and it is an M340, the issue could be that your IO module is set up for 'Mixed Topological and State RAM' which actually only supports the 'Flat' addressing. If that is the case you can change it to 'Topological' by double clicking on the IO module then left clicking on the module part number at the top left of the window and selecting the 'Memory' tab.

슈나이더 일렉트릭 Korea

자세히 알아보기

자세히 알아보기

도움이 필요하신가요?

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.