What are the switchgear control failure codes in Easergy T300?
Whenever a command is issued a code appears in the event log for each control operation. These are the following codes and the reasons indicating the status of each control operation.
| Main switchgear control failure variable | |
| Value (potential issue code) | Description |
| 0 | Command completed successfully |
| 1 | Local command blocked because switch position is intermediate or unknown |
| 2 | Local command blocked because switch position is already in correct state |
| 3 | Local command canceled by user |
| 4 | Switch position did not change within configured maximum operation time |
| 5 | Command blocked by Head Unit interlocks, e.g. potential motor supply issue or battery low |
| 6 | Command did not execute due to timeout waiting for enable from Head Unit |
| 7 | Local command blocked because disabled by configuration |
| 8 | Local command blocked because local/remote status is unknown |
| 9 | Local command blocked because local/remote status is remote |
| 10 | Local command blocked because automation is on |
| 11 | Remote command blocked because automation is on |
| 12 | Sectionalizer command blocked because automation is off |
| 13 | Sectionalizer command blocked because local/remote status is unknown |
| 14 | Sectionalizer command blocked because local/remote status is local |
| 15 | Unexpected command source (firmware potential issue) |
| 16 | Remote command blocked because requested position is not a valid value |
| 17 | Command blocked because a command is already in progress for this module |
| 18 | Command blocked because the power shutdown signal is active |
| 19 | Command blocked because a command is already in progress for another module |
| 20 | Command blocked because measured switch position is intermediate or unknown |
| 21 | Command blocked because measured switch position is the same as the requested position |
| 22 | Command blocked because ground (earth) switch position is not open |
| 23 | Open command blocked because external input is false |
| 24 | Open command blocked because external input is true |
| 25 | Close command blocked because external input is false |
| 26 | Close command blocked because external input is true |
| 27 | Commands blocked because module behaviour mode is off |
| 28 | Command blocked because switch controller is in local mode |
| 29 | Command blocked because switch controller local/remote input is undefined |
| 30 | Command blocked because protection trip lockout is active |
| 31 | Command blocked because the OPEN/CLOSE command is in progress |
| 32 | Command blocked because a self-test is in progress |