Is it possible to power the ATV630 or ATV930 drive with an external +24VDC power supply?
Issue:
Is it possible to power the ATV630 or ATV930 drive with an external +24VDC power supply?
Product Line:
Variable Frequency Drives
Environment:
Applies to ATV630, ATV930
Cause:
Need to power the electronics of the drive from a separate external +24Vdc source in the panel
Resolution:
Yes, use an external 24Vdc power supply and wire it to "P24" and "0V" terminals on the ATV630 and ATV930.
Note: You cannot run a drive with only 24VDC provided. Use an external 24V only to power the electronics of the drive for programming purposes.
Is it possible to power the ATV630 or ATV930 drive with an external +24VDC power supply?
Product Line:
Variable Frequency Drives
Environment:
Applies to ATV630, ATV930
Cause:
Need to power the electronics of the drive from a separate external +24Vdc source in the panel
Resolution:
Yes, use an external 24Vdc power supply and wire it to "P24" and "0V" terminals on the ATV630 and ATV930.
Note: You cannot run a drive with only 24VDC provided. Use an external 24V only to power the electronics of the drive for programming purposes.
게시 대상: 슈나이더 일렉트릭 Korea

