브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Details of 300 Hz Leakage current presence in the Variable speed drives (VSD).
Leakage current is caused by:
- "not-ideal" parameters of every insulation laying between living parts and ground
- components connected between living part (any phase) and ground by purpose, for example overvoltage protection, EMC filter, etc.

When speaking about VSD,, the leakage current has 2 parts:
1. Due to built-in EMC filter that is connected to the ground via capacitance, there is permanent constant part of leakage current at the same frequency as supply network. (50 or 60Hz). Note that built - in EMC filter can be disconnected from ground, which is especially required in IT networks
2. Due to ATV operation principle when potential on living parts (DC+, DC-, motor phases U.V,W) is permanently changed with high rise and fall (high dv/dt), there is current flown to the ground via stray capacitance. ic=C*dv/dt. Almost all ATVs have 3-phase input rectifier (also called 6-pulse bridge) which means that DC bus is regularly charged 6 times during 20ms (20ms is period of 50Hz supply), this result in dv/dt rise at the rectifier output with frequency 6-times AC supply frequency.
6pulses * 50Hz = 300Hz pulses in leakage current.

슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings