Is there an offset baying bracket or some way to bay cabinets of different depths?
Issue:
A customer is looking for an offset baying bracket for NetShelter SX cabinets.
Product Line:
NetShelter SX
Environment:
All models, all serial numbers.
Cause:
There's no way to bay NetShelter SX cabinets of different depths.
Resolution:
There's not an offset baying bracket, but ACDC2550 can be used to make a 1070 mm deep NetShelter SX cabinet be flush with a 1200 mm deep SX cabinet.
A customer is looking for an offset baying bracket for NetShelter SX cabinets.
Product Line:
NetShelter SX
Environment:
All models, all serial numbers.
Cause:
There's no way to bay NetShelter SX cabinets of different depths.
Resolution:
There's not an offset baying bracket, but ACDC2550 can be used to make a 1070 mm deep NetShelter SX cabinet be flush with a 1200 mm deep SX cabinet.