브랜드

Impact-Company-Logo-English Black-01-177x54

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
What is the FFB execution order on Unity Pro FBD section?
Issue
Some customers would like to know the execution order of FFB on Unity Pro FBD section, because sometimes they want that one FFB be executed before other.

Product Line
Control Expert / Unity Pro all versions.

Environment
This resolution was created using Unity Pro v13.0 running on Windows 10 version 1703.

Resolution
The execution order is determined by the position of the FFBs in the section (executed from left to right and from top to bottom) and is displayed with execution numbers on the top right corner of the FFB. When your logic has FFB inputs that comes from another FFB, the execution order will be as bellow:
  1. Execute from top to bottom all FFBs that don't have another FFB as input (on the left side)
  2. Execute from top to bottom all FFBs that have another FFB as inpput
​The picture bellow shows the execution order and you can see that the FFB 13 will be executed before the 11 that is above.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings