Enclosed ATS22 soft starter is not running in Auto mode.
Issue:
ATS22 Not Running in Auto Mode.
Product Line:
8639 22U enclosed ATS22
Environment:
All
Cause:
Auto start is not starting the soft starter.
Resolution:
Normally the auto start for auto is terminals 5-6. So the end customer will need to close a set of dry contacts on these terminals to start the unit in Auto mode.
You can find the basic wiring diagrams in the Enclosed Altistart 22 manual
https://www.schneider-electric.us/en/download/document/30072-453-26/
ATS22 Not Running in Auto Mode.
Product Line:
8639 22U enclosed ATS22
Environment:
All
Cause:
Auto start is not starting the soft starter.
Resolution:
Normally the auto start for auto is terminals 5-6. So the end customer will need to close a set of dry contacts on these terminals to start the unit in Auto mode.
You can find the basic wiring diagrams in the Enclosed Altistart 22 manual
https://www.schneider-electric.us/en/download/document/30072-453-26/
게시 대상: 슈나이더 일렉트릭 Korea

