How do I break down an ATV660 part number to determine size, voltage, options, etc?
Issue:
ATV660 part number break down
Product Line:
Altivar 660 enclosed drives
Environment:
All
Cause:
Need to break down a part number
Resolution:
This information is located in the ATV660 Instruction Manual, which can be found here.
The options tables start in Section 2- Product Characteristics. Use the tables to go through the part number by each option.
The bulletin is also attached to this article.
Catalog Number Example: ATV660D22T4N2ANWAANAGK
| Field | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|
| 01–02 | 03–04 | 5 | 6 | 7 | 8 | 9 | 10 | 11 | 12 | 13 | 14 |
| ATV660 | D22 | T4 | N | 2 | A | N | W | A | A | N | A, G, K |
| Altivar 660 Process Drive | 3 hp | 460 V, 3 phase | Normal Duty Power Rating | UL Listed | UL Type 12K Enclosure | No Harmonic Mitigation | Without Bypass | H-O-A Speed Pot. | Red Power On, Yellow Tripped, Green AFC Run, Yellow Auto | No Comm. Card | Ethernet Port in Front Door; Type 1 SPD; Additional 150 VA Control Power |
| Field | Digit | Characteristic | Description | |
|---|---|---|---|---|
| 01–02 | 1–6 | Drive Style | Altivar 660 Process Drive, 2-quadrant, 6-pulse drive | |
| 03–04 | 7–9 | Power Rating (kW) | Normal Duty U07 = 1 hp U15 = 2 hp U22 = 3 hp U40 = 5 hp U55 = 7.5 hp U75 = 10 hp D11 = 15 hp D15 = 20 hp D18 = 25 hp D22 = 30 hp D30 = 40 hp D37 = 50 hp D45 = 60 hp D55 = 75 hp D75 = 100 hp D90 = 125 hp C11 = 150 hp C13 = 200 hp C16 = 250 hp C20 = 300 hp C25 = 400 hp C31 = 500 hp C40 = 600 hp C50 = 700 hp C63 = 900 hp | Heavy Duty U15 = 1 hp U22 = 2 hp U30 = 3 hp U55 = 5 hp U75 = 7.5 hp D11 = 10 hp D15 = 15 hp D18 = 20 hp D22 = 25 hp D30 = 30 hp D37 = 40 hp D45 = 50 hp D55 = 60 hp D75 = 75 hp D90 = 100 hp C11 = 125 hp C13 = 150 hp C16 = 200 hp C20 = 250 hp C25 = 300 hp C31 = 400 hp C40 = 500 hp C50 = 600 hp C63 = 700 hp |
| 05 | 10–11 | Voltage Class | P3 = 208 V, Three Phase | |
| 06 | 12 | Duty Rating | N = Normal Duty | |
| 07 | 13 | Region | 2 = UL Marking | |
| 08 | 14 | Enclosure Type | G = Type 1 General Purpose | |
| 09 | 15 | Line Harmonic Mitigation | N = None | |
| 10 | 16 | Power Circuit | S = Integral Softstart Bypass | |
| 11 | 17 | Control Options | N = Prewired for Remote H-O-A | |
| 12 | 18 | Light Options | N = None | |
| 13 | 19 | Communication Card | N = None | |
| 14 | Varies | Miscellaneous Options | A = Ethernet Port in Front Door | |