브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Length of the wire to connect analog I/O of two PM8000 meters

Issue

To wire analog output(s) of one meter to the analog input of the other meter.

Product Line
ION and PowerLogic Meters

Environment

ION Setup
Meter Front Panel


Resolution

The user may want to wire the analog output of one PM8000 meter to the analog input of the other PM8000 meter, these meters could be located at some distance from each other.

The meter's analog I/O option modules can measure either low voltage or current using standard analog transducers such as 4 - 20 mA current transducers.

For an analog input operation, your meter takes an analog input signal and provides the resulting scaled value. For an analog output operation, your meter takes an input value and scales it to the appropriate signal value to send out the physical analog output port. You can view analog I/O values from your meter’s display or web pages.

The wire that connects the analog output of one meter to the analog input of other meter presents resistance to current, more length means more resistance, this will lead to a decrease in current. The user can still read some value on analog inputs of the meter if it is within 4 - 20 mA analog input range.

On the remote display or the front panel, scroll up and locate Inputs/Outputs--->Analog Inputs to read values.



슈나이더 일렉트릭 Korea

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings