오늘 무엇을 도와드릴까요?

What can cause an bLF or brake control fault on the ATV630 and ATV930 Process drives?

Issue:
Posible cause of a bLF Fault on ATV630/930.

Product Line:
ATV630 and ATV930 Process drives

Environment:
All

Cause:
Wrong setting of the parameter IBR (Brk Release Current)
Bad fluxing of motor ( 5*tr ).(tr = Rotor time constant).
Incorrect values of auto tuning (check in expert mode TRM).


Resolution:
Principle:
This fault appears when the brake logic is used and the conditions to open the brake are not
present.
If the brake release current (parameter IBR) is not attained after a delay (parameter
BRR+100ms) or it is impossible to flux the motor during 5*tr ( tr = Rotor time constant ) then
the fault appears.
Probable cause:
- wrong setting of the parameter IBR (Brk Release Current)
Bad fluxing of motor ( 5*tr ).(tr = Rotor time constant).
Incorrect values of auto tuning (check in expert mode TRM).
Remedies:
Check the drive/motor connections.
Check the motor wending
Check the IBR (current for brake opening while ascending) and IRD (current for brake opening
while descending) settings.
Check the setting of bEn (brake closing frequency)
Check the parameter BRR   Current ramp time ( only in expert mode ).

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings