브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Why are my ATV340 parameters lost when I cycle power if I've written them over the network?

Article available in these languages: 스페인어

​Issue:
Parameters lost when power cycling

Product Line:
Altivar 340

Environment:
ALL

Cause:
Programming Wiring

Resolution:
When changing a parameter over any network connection, the new setting is active in the operating memory of the drive (RAM).
When power is cycled the RAM memory is overwritten by the permanent memory (EEPROM) as part of the power up process.
To have changed values permanently saved you must tell the drive to write the RAM memory to the EEPROM.  This is done by changing bit 1 of the CMI word from 0 to 1.
The drive will automatically reset the bit to 0 once the save process has been completed.

Caution must be used when writing to the EEPROM in this manner.  The memory has a limited number of writes available and if that number is exceeded the drive will experience a memory failure, preventing the drive from operating.
d
This limitation is also present on other drives although the exact number of write operations may be different.  Consult the drive communication documentation for specific details.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
카테고리:
자세히 알아보기
제품군
카테고리:
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings