Issue:
Use Terminals for Start/Stop and Dial for Speed Ref on ATV32
Product Line:
Altivar 32
Environment:
All
Cause:
N/A
Resolution:
Go into CONF, FULL, CTL menu.
Set CHCF to SEP (hold 2 seconds)
FR1 to A1U1.
CD1 to TER.