Power Monitoring Expert 8.x/9.0 - Some of the ION services will not start - 'Error 1053 - The service did not respond to the start or control request in a timely fashion'

Issue
In some environments, some ION services will fail to start after rebooting or restarting manually. The affected services by software version are:


Product Line
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0

Environment
At this time, it is not entirely clear why this only happens in some systems. It seems to correlate to some Windows Updates.

Power Monitoring Expert 9.0

  • ION Application Modules Core Services Host
  • ION Cloud Agent Service
  • ION Managed Circuit Service
  • ION Diagnostic and Usage Service
  • ION Log Subsystem Router Service
  • ION Software Data Processing Service
  • ION Software Modbus Gateway Service

Power Monitoring Expert 8.x

  • Application Modules CoreServicesHost
  • ION Diagnostic and Usage Service
  • ION Managed Circuit Service
  • ION Software Alarm Service
  • ION Software Modbus Gateway Service

You will see a popup error that states:
'Windows could not start the ION <service name> service on the Local Computer.
Error 1053: The service did not respond to the start or control request in a timely fashion


Cause
When signed .Net service executables start, an attempt is made to verify the digital signature. If this attempt takes longer than 30 seconds, the Windows Service Control Manager (SCM) does not allow the service to start, and you will see the error described above. It was recommended by Microsoft that this check be disabled prior to .Net Framework 4 and later via a setting in the service's config file, which is what was done in the older ION services. Microsoft stated that this was unnecessary when using the .Net framework 4.0 and later, so newer ION services did not include this element in the config files.

See this link for more information:
https://docs.microsoft.com/en-us/dotnet/framework/configure-apps/file-schema/runtime/generatepublisherevidence-element

In spite of what is said in the link above, it now seems that in some environments this config element is still necessary.

Resolution

*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).

This problem can be easily resolved by adding the element below to the affected ION service config file. Updated files are attached. There is a package for PME 8.2, and also for PME 9.0.

<configuration>
<runtime>
<generatePublisherEvidence enabled="false"/>
</runtime>
</configuration>


Note that the ION Diagnostic and Usage Service and ION Software Modbus Gateway Service do not have .config files, so they need to be added.
The required files are attached. There is a package for PME 8.2, and also for PME 9.0.

Deployment Instructions
Be sure to stop all ION services before deploying!
Extract the zip file corresponding to your PME version and copy these files and their folders into the Power Monitoring Expert directory, replacing the existing files.


Note: This issue was fixed in PME 2020.

슈나이더 일렉트릭 Korea

첨부 파일
PME8.x.zip [7.16 KB]
PME9.zip [9.42 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군

도움이 필요하신가요?

도움이 필요하신가요?

제품 선택기

제품 선택기

애플리케이션에 적합한 제품과 액세서리를 빠르고 쉽게 찾을 수 있습니다.

견적 받기

견적 받기

영업 관련하여 온라인으로 문의하시면 전문가가 연락드립니다.

구매처

구매처

해당 지역의 가장 가까운 슈나이더 일렉트릭 대리점을 쉽게 찾을 수 있습니다.

지원 센터

지원 센터

한 곳에서 모든 요구 사항에 대한 지원 리소스를 찾아보십시오.

  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings