브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
How to see real time values in an ION meter’s advanced module registers?

Issue
A user may require seeing real time values in an ION module registers.

Product line
ION Setup

Environment
ION Setup

Cause
A user may require seeing real time values in the advanced ION module registers, instead of updating the values by re-clicking on the register tabs.

Resolution
In ION Setup:

  1. Switch to advanced mode by holding down the Ctrl and left clicking on the mouse.
  2. Open the desired module folder, and navigate to the module.
  3. If prompted enter the meter’s password.
  4. Hold shift and left click on the Output Registers tab.  This will switch the module into value mode.
  5. By default, the registers are set to update by click only.​
  6. To change this right-click on the Output Registers tab and select the desired update interval. Available options are every second, 5 seconds, 10 seconds, and 30 Seconds. ​


ion setup

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings