What would cause the ATV630 (or ATV930) M/S configured drives (Multidrive) not to start?
Issue:
Customer has 2 or more Altivar Process drives in a MultiDrive M/S configuration that will not start when the run command is issued.

Product Line:
ATV600 series drives; ATV630, ATV650, ATV660, ATV680, APM
ATV900 series drives; ATV930, ATV950, ATV960, ATV980, APM

Environment:
M/S function using Multidrive Configuration

Cause:
Run command sequence incorrect.

Resolution:
On the ATV Process drives configured for M/S configuration, it is necessary that the run command be present on all slave devices before  a run command is issued to the main drive. If a run command is issued to the main drive before all secondary devices have a command the drives will not start.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:
Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:
Support | Schneider Electric Global (se.com)

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings