How to fix problem when TSXCUSB485 or TSXCUSB232 cable is not recognized by windows 10?

Article available in these languages: Czech, 그리스어, 헝가리어, 네덜란드어

Issue
Windows 10 doesn't recognize the connection cable TSXCUSB485 or TSXCUSB232.

Product Line
EcoStruxure Control Expert, TSXCUSB485, TSXCUSB232

Environment
TSXCUSB485, Windows 10

Resolution
Be sure you have administrator rights. The most probable reason is that windows provides the driver from windows update site instead of using the driver from SchneiderModbusDriverSuite (part of Unity Pro/ControExpert installation).
  1. In Device manager, uninstall TSX cable driver (in Serial USB folder) when TSXCUSB485/TSXCUSB232 cable is plugged in.
  2. Open Control Panel>> System>> Advanced system settings>> Hardware>> Device installation setting and select "no" for the option "Do you want to automatically download manufacturers apps and custom icons available for your device?"
  3. Uninstall Driver Manager x64. (search DriverManager x64 in registry HKEY_LOCAL_MACHINE\Software\Microsoft\Windows\CurrentVersion\Uninstall, then copy the uninstall string (msexec...) and run it
  4. Unplug the TSX cable, restart PC
  5. Run "Turn windows features on or off" and check if microsoft  .NET framework is enabled including 2 sub options (Foundation HTTP activation, Framework activation)
  6. Install the driver (schneiderModbusDriverSuite 14_12 or newer) or re-install Unity Pro completely.
  7. Plug in TSX cable and check in device manager if the cable appears in com port folder. If so, problem is solved.
P.S.: You can see the drivers inside of the instalation folder:
image

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings