브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Can we replace BRS364 by BRS307 as we need shaft with key?
BRS364 has smooth shaft as standard. Specific shaft (S) is only on request, see first page in catalog extract. Specific request means that customer has to ask directly factory in Lahr for the price offer.
BRS397 can be ordered with either smooth shaft or keyed shaft, see second page.
Motor 397 itself can generate enough torque (as it i stronger than BRS364), though due to greater inertia it cannot achieve the same max speed, see comparison.
Before replacement two facts must be considered:
- speed range required by application
- a driver. Brs397 consumes more current so existing driver used for 364 could be overloaded.
See attachment with:
BRS motor reference description,
comparison between BRS364, 397 in torque/speed and inertia.
Driver sizing for BRS

슈나이더 일렉트릭 Korea

첨부 파일
BRSxxx.zip [440.5 KB]
자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings