브랜드

슈나이더 일렉트릭 코리아 웹사이트에 방문해 주셔서 감사합니다.

슈나이더 일렉트릭 코리아 웹사이트 방문자 분들 모두 환영합니다.
		
오늘 무엇을 도와드릴까요?
Local NetBotz Camera Pod 165 Does not Appear in the Appliance Web UI
Issue:
If you move the camera pod from your company network (a remote connection) to the appliance’s private network (a local connection), the camera pod does not appear in the Web UI of the appliance.

Product Line:
NetBotz 5.x
NBPD0165

Cause:
The camera pod retains the IP address lease from your company’s network for a period of time (which varies by company) before it acquires a new DHCP lease from the appliance. Until the Camera Pod acquires a new lease from the appliance, it does not appear in the Web UI

Resolution:
Reset the Camera Pod 165 to force it to acquire a new lease immediately. Press the reset button for at least 30 seconds (until the top Network LED on the camera pod turns off). Then wait about 5 minutes for the appliance to reconnect to the camera. Do not disconnect the camera pod from power during this time.

슈나이더 일렉트릭 Korea

자세히 알아보기
제품군
자세히 알아보기
제품군
  • 제품 문서
  • 소프트웨어 다운로드
  • 제품 선택기
  • 제품 대체 및 교체
  • 지원 및 연락처 센터
  • 영업소 검색
  • 견적 받기
  • 슈나이더 일렉트릭 커뮤니티
  • 채용
  • 회사 소개
  • 부정 행위 보고
  • 접근성
  • 뉴스룸
  • 투자자
  • Ecostruxure
  • 작업 검색
  • 블로그
  • 개인정보 취급방침
  • 쿠키 공지
  • 사용 약관
  • Change your cookie settings