Can the Altivar Process analog values be read over Ethernet if the inputs are not assigned?

Issue:
Is it possible to Read an Analog input status via Ethernet.

Product line:
Altivar Process 600 and 900 series

Resolution:
Yes, the values of the analog inputs can be read by checking the appropriate register values found in the Communication Parameters spreadsheet.  The analog input does not need to be assigned to any function.